Abstract

Such basic concepts of power theory as apparent power, active current and minimum power losses in the transmission line are defined for a three-phase three-wire system in the shortened two wattmeter reference frame. On the basis of these concepts, two energy-efficient active filtration strategies were developed and verified by virtual experi- ments. The first of them minimizes the power losses of a three-phase three-wire transmission line with different values of its resistances and ensures a unit value of the power factor. The second strategy follows the recommendation of IEEE Std. 1459- 2010 ensures the minimum power loss of the transmission line with symmetrical sinusoidal currents of a three-phase source.

Description

Keywords

three-phase three-wire power supply system, apparent power, active current, energy-efficient strategies of ac- tive filtering, two wattmeter reference frame, two wattmeter reference frame, трифазна трипровідна система живлення, повна потужність, активний струм, енергоефективні стратегії активної фільтрації, система координат методу двох ватметрів